REON Support
NEW UNIT / SITE INSTALLATION NOT GETTING ONLINE
When a new unit is installed at a site for the first time, follow these steps:
- Prior to powering on the unit, verify the availability of SIM cards. It is advisable to have two SIMs to mitigate potential network issues.
- Inspect and confirm the data on both SIMs. If they are malfunctioning or exhibit weak signals, replace them with a network that has better coverage at the site.
- Instruct the team to insert the SIMs into the unit, securely mount the unit in the cabinet, and connect all necessary cables before powering it on. This will expedite the process and help the unit come online more quickly.
- Turn ON VPN Config on Web page.
- Check the unit's IP address, connect to the VPN, and open the command prompt on your laptop by pressing WIN + R and typing cmd. Then enter
ping IP -twhere IP should resemble10.X.X.X - If a response is received, access the device’s portal through a web browser, configure the basic settings (e.g., check mapping from the user portal – remove spacing and re-verify) and the unit will come online on Spark.
- If the steps outlined above do not bring the unit online, please forward this site to the Encore team for additional troubleshooting assistance.
RMS OFFLINE ISSUE / RMS NOT GETTING ONLINE ON SPARK
This is a common issue encountered in support. Here’s how to address it:
Level 1 support (SOC) needs to follow some steps:
- Provide the basic information of the site, including the site ID (e.g., EC1-LHR-02002)
- Include the RMS serial number (e.g., REON10020).
- Share the remote access ID (Anydesk / Rustdesk).
- Avoid performing a hard reset on the unit initially; Encore support will request this only after completing basic troubleshooting.
- Verify the data on both SIMs. If they are not functioning or have weak signals, replace them with a network that offers better coverage at the site.
- Check if SIM switching is occurring every 10 minutes based on the current time. If it is not, report this to the Encore team for further troubleshooting.
- If basic troubleshooting fails, escalate the site to the Encore team for further investigation.
RECTIFIER IS OFFLINE / SOLAR DATA NOT RECEIVED FROM THE RECTIFIER
- Check which rectifier is selected in portal and their live data is updating with current time or not.
- Ping the rectifier from the laptop.
- If ping is not received then rectifier is not connected, or it is offline. As in this case it is Vertiv.
- If ping is received then rectifier is connected to ACCU. As in this case it is Vertiv.
- Incase if Vertiv if ping is received but data is still not sent then activate the SNMP and Modbus in Vertiv rectifier page.
- Access the rectifier page by add :8080 after the ACCU Ip.
10.42.0.2:8080
- Go to the Advance setting page then go to SNMP tab.

- Configure the setting in NMSV2 Configuration section. The configuration should as the following:
- If configuration is different than Delete this and set new configuration.
NMS IP: 10.42.0.1 Public Community: public Private Community: private Trap Enabled: Enabled

- Also activate the Modbus configuration

- Then check if data if sending.